4-216
11- 51
Braking Selection of Zero Speed
Range
0: Disable
1: Enable
11-51: Operation selection of zero-speed braking
In V/F control mode, the DC braking operation can be used to the motor shaft.
Set 11-51 to select zero-speed braking operation to 1 to enable this function.
To use DC braking operation set parameter 00-02 (operation command selection) to 1 and parameter
00-05 (frequency reference selection) to 1, the operation command and frequency reference are now set
for external control. When the frequency reference is 0V (or less than 4mA), and the operation command is
turned on, the zero-speed ‘DC’ braking operation is activated and holding torque is generated using DC
braking.
Refer to Fig.4.4.84 for more information on zero-speed DC braking operation.
Note: DC braking 07-07 is limited to 20% of the inverter rated current.
Figure 4.4.84 Zero-speed braking operation
11- 54
Initialization of Cumulative Energy
Range
0: Do not Clear Cumulative Energy
1: Clear Cumulative Energy
Reset the cumulative energy (KWHr) (12-67) and the cumulative energy (MWHr) (12-68) via parameter
11-54.
11- 55
STOP Key Selection
Range
0
: Stop Key is Disabled when the Operation Command is not Provided by
Keypad.
1: Stop Key is Enabled when the Operation Command is not Provided by
Keypad.
11-55= 0: Stop button disabled when operation command is set for terminals (00-02=1) or communication
(00-02=3).
11-55= 1: Stop button enabled.