4-217
11- 56
UP/DOWN Selection
Range
【
0】: When UP/DOWN in Keypad is Disabled, it will be Enabled if Pressing ENTER
after Frequency Modification.
【1】: When UP/DOWN in Keypad is Enabled, it will be Enabled upon Frequency
Modification.
11-56= 0: Changing the reference frequency on the keypad in UP/DOWN control requires the ENTER
button to be pressed for the inverter to accept the modified reference frequency.
11-56= 1: Changing the reference frequency on the keypad in UP/DOWN control immediately changes the
reference frequency and there for the output frequency.
Note: The reference frequency can be changed (up or down) via the keypad or by setting one of
multi-functional digital input terminals (03-00 to 03-05) to 8 and 9. Refer to instructions of
(03-00 to 03-05 = 8 or 9).
11- 58
Record Reference Frequency
Range
【
0】: Disable
【1】: Enable
This function is enabled only when one of multi-function digital input terminals (03-00 to 03-07) is set to 11
(ACC / DEC Inhibition command).
11-58= 0: When ACC / DEC inhibition command is enabled, the motor will stop accelerating or
decelerating and the frequency at the moment will be used as frequency command. If ACC / DEC inhibition
command is disabled or stop command enabled, the frequency command will set to original frequency.
Besides, when stop command enabled, or the power is cut off and reset. The frequency will be set to 0 Hz
Note: If ACC/DEC inhibition command is enabled before running, it will display STP0 after running, due to
there is no reference frequency record.
11-58= 1: When ACC / DEC inhibition command is enabled, the output frequency will be recorded and to
be used as frequency command. When it switches to stop or the power is cut off and reset, the ACC / DEC
inhibition command is still enabled, the frequency command is still recorded and the frequency command
is set to the frequency that was recorded.
Please refer to the following figure.