Gain of Preventing Oscillation
Range
【0.00~2.50】
Gradually increase the setting value with the unit of 0.01 when the motor is driven leading to the
occurrence of oscillation under the state of normal duty.
11- 60 Upper Limit of Preventing Oscillation
Range
【0~100】%
Function of prevention of oscillation upper limit is required to be within the setting value.
11- 61
Time Parameter of Preventing Oscillation
Range
【0~100】
Adjust the response of oscillation function. That is, adjust once delay time parameter of prevention
oscillation function.
11- 62
Prevention of Oscillation Selection
Range
【0】: Mode 1
【1】: Mode 2
【2】: Mode 3
When 11-62 is set to 0 and 1, the response to prevention oscillation is slower.
When 11-62 is set to 2, the response to prevention oscillation is faster.
11- 63
Flux- Strengthening Selection
Range
【0】: Disable
【1】: Enable
11-63=0: It has no function of flux-strengthening, the no-load current of high speed and low speed are the
same.
11-63=1: It has function of flux-strengthening, the torque of low speed is higher, but the no-load current is
also higher, it is suitable for big load in low speed.
11- 69 Gain of Preventing Oscillation 3
Range
0.00~200.00 %
Adjust the response of Gain of Preventing Oscillation 3
If vibration with motor in ND mode occurs, please increase by 0.01 unit to set.
11- 70
Upper Limit of Preventing Oscillation 3
Range
0.01~100.00 %
It is required to limit the preventing oscillation 3 upper limit within the setting value.
11- 71 Time Parameter of Preventing Oscillation 3
Range
0~30000 ms
Adjust the response of oscillation 3 function. (Time parameter of adjust preventing oscillation function
delay.)
11- 72 Switch Frequency 1 for Preventing Oscillation Gain
Range
0.01~300.00 Hz
11- 73 Switch Frequency 2 for Preventing Oscillation Gain
Range 0.01~300.00 Hz
Refer to the following figure for the setting of parameters 11-72 and 11-73.