4
-229
Multi-function digital input terminal S1 controls forward operation / stop command, and S2 controls reverse
operation / stop command. Refer to Figure 4.4.1. The input voltage (01-14) will be set to 230V (200V class)
or 400V (400V class) automatically and when 01-00 (V/F curve) is set to F, the maximum frequency of
01-12 will be set to 50Hz automatically.
13-08=14: 3 wire initialization (230V/460V, 50Hz)
Multi-function digital input terminal S7 controls the forward / reverse direction, and terminals S1 and S2 are
set for 3-wire start operation and stop command. Refer to Figure 4.4.2 and Figure 4.4.3 for 3-wire type
operation mode. The input voltage (01-14) will be set to 230V (200V class) or 400V (400V class)
automatically and when 01-00 (V/F curve) is set to F, the maximum frequency of 01-12 will be set to 50Hz
automatically.
13-08=15: 2 wire initialization (220V/380V, 50Hz)
Multi-function digital input terminal S1 controls forward operation / stop command, and S2 controls reverse
operation / stop command. Refer to Fig.4.4.1. The input voltage (01-14) will be set to 220V (200V class) or
380V (400V class) automatically and when 01-00 (V/F curve) is set to F, the maximum frequency of 01-12
will be set to 50Hz automatically.
13-08=16: 3 wire initialization (220V/380V, 50Hz)
Multi-function digital input terminal S7 controls the forward / reverse direction, and terminals S1 and S2 are
set for 3-wire start operation and stop command. Refer to Figure 4.4.2 and Figure 4.4.3 for 3-wire type
operation mode. The input voltage (01-14) will be set to 220V (200V class) or 380V (400V class)
automatically and when 01-00 (V/F curve) is set to F, the maximum frequency of 01-12 will be set to 50Hz
automatically.
Note: Restore factory setting (13-08) will not modify the setting of 01-00 (V/F curve).
Parameter List: parameters that are not affected by default value
No.
Parameter Name
00-00 Control Mode Selection
00-04 Language Selection
01-00 V/F Curve Selection
13-00 Inverter Rating Selection
13-03 Cumulative Operation Hours 1
13-04 Cumulative Operation Hours 2
13-05 Selection of Accumulative Operation Time
13- 09
Fault History Clearance Function
Range
【0】:
Do not Clear Fault History
【1】:
Clear Fault History
13-09=1: Clear inverter fault history including (12-11~12-15/12-45~12-64)
13- 10
Parameter Password Function 2
Range
0 ~ 9999
13- 11
C/B CPLD Ver. *1
Range
【0.00~9.99】
This parameter displays CPLD version on the control board.