4-235
16- 05
LCD Backlight
Range 0~7
Adjust the screen contrast of the digital operator. If it is set to 0, the screen backlight is turned off.
16- 07
Copy Function Selection
Range
0: Do not copy parameters
1: Read inverter parameters and save to the operator.
2: Write the operator parameters to inverter.
3: Compare parameters of inverter and operator.
16- 08
Selection of Allowing Reading
Range
0: Do not allow to read inverter parameters and save to the operator.
1: Allow to read inverter parameters and save to the operator.
LCD digital operator with built-in memory (EEPROM) can be used to store and retrieve parameters:
(1) Read: Save inverter parameters to the digital operator (INV OP).
(2) Write: Write the parameters from the digital operator to the inverter and save (OP INV).
(3) Verify: Compare the inverter parameters against the parameters in the digital operator.
16-07=0: No action
16-07=1: Read (all parameters are copied from the inverter to the keypad).
16-07=2: Write (all parameter are copied from the keypad to the inverter).
16-07=3: Verify (Compare the set value of the inverter to the parameter of the digital operator).
Set 16-08 = 0, to prevent the saved parameter data stored in the digital operator from accidentally being
overwritten.
When parameter 16-08=0 and the read operation is executed (16-07=1) a warning message of "RDP
Read Prohibited" will be displayed on the keypad and the read operation is cancelled.
Refer to the following steps for copy function operation.
For the write-in operation requires the following items to match.
(1) Software version
(2) Control method
(3) Inverter type
(4) Inverter rated capacity and voltage
Set one of the parameters 03-00 to 03-05 (multi-function digital input selection) to 49 (Enable the
parameter write-in function) to enable or disable the parameter write-in function.
When terminal is active, parameters can be copied from the digital operator to the inverter. When the
terminal is not active inverter parameters are prohibited from write-in, excluding the reference frequency
(00-05).
Note: Parameter 16-11 (RTC date setting) and 16-12 (RTC time setting) require resetting, after parameter
setting in the keypad is written and saved in the inverter (OPINV).