4-240
xx0x B: RTC Run2 Forward Rotation xx1x B: RTC Run2 Reverse Rotation
x0xx B: RTC Run3 Forward Rotation x1xx B: RTC Run3 Reverse Rotation
0xxx B: RTC Run4 Forward Rotation 1xxx B: RTC Run4 Reverse Rotation
Source of timer can be selected to link multiple time periods and one time period can be set to multiple
timers.
Timer is set by the following steps:
Start the timer:
Timer starts via the setting of RTC timer function (16-13).
Set the time period:
Set the start & stop time and date. If the setting of start time is equal to that of stop time, timing period is
off.
The timer is enabled:
Arrange time period to the specific timer (16-32~16-35).
Link to parameters:
The timer can be linked to the relay output. One relay output can be only linked to one timer( ex. 03-11,
03-12 and 03-39, 16-36).
Note: If the stop time is set to 12:00, Motor start to stop from 12:01.
Refer to Fig.4.4.86 for RTC structure.
Step 1 Step 2 Step 3 Step 4
(Start the Timer)
( Set the Time Interval)
( Timer is Enabled)
( Link to Parameters)
Start/Stop
Timer
(G16- 13)
Time period 1
(G16- 14 - 17)
Time period 2
(G16- 18 - 21)
Time period 3
(G16- 22 - 25)
Time period 4
(G16- 26 -29)
Offset Time
(G16- 31)
Offset Time is
On/Off
(G16- 30)
Timer 1
(G16- 32)
Timer 2
(G16- 33)
Timer 3
(G16- 34)
Timer 4
(G16- 35)
.G16- 36 (RTC Speed Selection)
.G03- 11Relay output (R1A - R1C)
.G03- 12Relay output (R2A - R2C)
.G03- 39Relay output (R3A - R3C)
Figure 4.4.86 RTC structure
Refer to the following Table 4.4.13 for the selection of timer operation cycle.
Table 4.4.13 Arrange time period to the timer function
16-32
~
16-35
O P4 P3 P2 P1 Timer Function Display
0 0 0 0 0 0 Without the selection of timer None
1 0 0 0 0 1 Time Period 1 P1
2 0 0 0 1 0 Time Period 2 P2
3 0 0 0 1 1 Time Period 1 and 2 P1+P2
4 0 0 1 0 0 Time Period 3 P3
5 0 0 1 0 1 Time Period 1 and 3 P1+P3
6 0 0 1 1 0 Time Period 2 and 3 P2+P3
7 0 0 1 1 1 Time Period 1 , 2 and 3 P1+P2+P3
8 0 1 0 0 0 Time Period 4 P4
9 0 1 0 0 1 Time Period 1 and 4 P1+P4
10 0 1 0 1 0 Time Period 2 and 4 P2+P4
11 0 1 0 1 1 Time Period 1 , 2 and 4 P1+P2+P4