4-241
16-32
~
16-35
O P4 P3 P2 P1 Timer Function Display
12 0 1 1 0 0 Time Period 3 and 4 P3+P4
13 0 1 1 0 1 Time Period 1 , 3 and 4 P1+P3+P4
14 0 1 1 1 0 Time Period 2 , 3 and 4 P2+P3+P4
15 0 1 1 1 1 Time Period 1 , 2 , 3 and 4 P1+P2+P3+P4
16 1 0 0 0 0 Offset selection Offset (O)
17 1 0 0 0 1 Offset and time period 1 O+P1
18 1 0 0 1 0 Offset and time period 2 O+P2
19 1 0 0 1 1 Offset and time period 1 and 2 O+P1+P2
20 1 0 1 0 0 Offset and time period 3 O+P3
21 1 0 1 0 1 Offset and time period 1 and 3 O+P1+P3
22 1 0 1 1 0 Offset and time period 2 and 3 O+P2+P3
23 1 0 1 1 1 Offset and time period 1 , 2 and 3 O+P1+P2+P3
24 1 1 0 0 0 Offset and time period 4 O+P4
25 1 1 0 0 1 Offset and time period 1 and 4 O+P1+P4
26 1 1 0 1 0 Offset and time period 2 and 4 O+P2+P4
27 1 1 0 1 1 Offset and time period 1 , 2 an 4 O+P1+P2+P4
28 1 1 1 0 0 Offset and time period 3 and 4 O+P3+P4
29 1 1 1 0 1 Offset and time period 1 , 3 and 4 O+P1+P3+P4
30 1 1 1 1 0 Offset and time period 2 , 3 and 4 O+P2+P3+P4
31 1 1 1 1 1
Offset and time period 1 , 2 , 3
and 4
O+P1+P2+P3+P4
Reference frequency and motor rotation direction are controlled by RTC function.
16-36=0: RTC speed selection is disabled.
16-36=1: Timer 1 is enabled.
Reference frequency = Frequency Setting of Speed-Stage 0 (05-01)
16-36=2: Timer 2 is enabled.
Reference frequency = Frequency Setting of Speed-Stage 0 (05-01)
16-36=3: Timer 3 is enabled.
Reference frequency = Frequency Setting of Speed-Stage 0 (05-01)
16-36=4: Timer 4 is enabled.
Reference frequency = Frequency Setting of Speed-Stage 0 (05-01)
16-36=4: Timer 1 and 2 are enabled.
Reference frequency is enabled by the simultaneous operation of timer 1 and 2.
Notes:
- The inverter runs via the start of the specific timer without the influence of other timers.
- The selection of RTC speed setting (16-36) is affected by the action of time period 1 to 4 (P1~P4)
which is corresponding to the selection of RTC rotation direction (16-37).
For example:
When the selection of RTC speed is set to 5 (by timer 1+2), source of run command (00-02) and
source of frequecny command (00-05) are required to set to RTC. Thus, reference frequency is
controlled by RTC timer 1 and 2 and the inverter continues running.
Refer to Table 4.4.14 for the control of reference frequency.
Note: Selection of RTC Rotation Direction (16-37) is limited by the Motor Direction Lock Selection(11-00).