4-244
Time gap
(G16- 31)
t
Multi-function digital input
(G03- 00 to 03- 05 = 56)
Offset Time
t
Figure 4.4.88 Operation of offset time
For example:
Inverter runs at the time period exclusive P1:
When 16-36=1 (selection of RTC speed is set to timer 1) and 16-32=17 (offset + PI), RTC offset (16-30) is
set by DI and the offset time is set via 16-31. Switch on DI and RTC will immediately start up.
If the source of timer is set to 15 (P1+P2+P3+P4), press “STOP key at the time period 1 (P1). Normally,
RTC will start automatically at the next time period (P2) but it can also start via the setting of 16-30 to 2 (set
by DI). Inverter re-runs when switching on DI and RTC will immediately start up.
Notes:
If press “STOP” key at the time period and inverter can re-run at this time, user can:
- Set the selection of RTC offset (16-30) to 2 (set by DI) and set DI to 56 (RTC Offset Enable).
- Switch the selection of RTC offset (16-30) to be enabled.
Note:
RTC Accuracy:
Temperature Deviation
+25(77) +/-3 sec./ day
-20 / +50 (-4/ 122) +/-6 sec./ day