4-245
Group 17: IM Motor
utomatic Tunin
Parameters
17- 00
Mode Selection of Automatic Tuning
Range
【
0】: Rotation Auto-tune
【1】: Static Auto-tune
【2】: Stator Resistance Measurement
【4】: Loop Tuning
【5】: Rotational Auto-tuning Combination (Item: 4+2+0)
【6】: Static Auto-tuning Combination (Item: 4+2+1)
17- 01
Motor Rated Output Power
Range
【0.00~600.00】KW
17- 02
Motor Rated Current
Range
10%~200% of the inverter rated current in V/F control mode
25%~200% of the inverter rated current in SLV control mode
17- 03
Motor Rated Voltage
*1
Range
200V:【50.0~240.0】V
400V:【100.0~480.0】V
17- 04
Motor Rated Frequency
*2
Range
【4.8~599.0】Hz
17- 05
Motor Rated Speed
Range
【0~24000】rpm
17- 06
Pole Number of Motor
Range
【2~16】pole (Even)
17- 08
Motor No-load Voltage
Range
200V:【50~240】V
400V:【100~480】V
17- 09
Motor Excitation Current
Range
【0.01~600.00】A (15%~70% motor rated current)
17- 10
Automatic Tuning Start
Range
【0】: Disable
【1】: Enable
17- 11
Error History of Automatic Tuning
Range
【0】: No Error
【1】: Motor Data Error
【2】: Stator Resistance Tuning Error
【3】: Leakage Induction Tuning Error
【4】: Rotor Resistance Tuning Error
【5】: Mutual Induction Tuning Error
【6】: Reserved
【7】: DT Error
【8】: Motor Acceleration Error
【9】: Warning
17-12
Leakage Inductance Ratio
Range
【0.1~15.0】%
17-13
Slip Frequency
Range
【0.10~20.00】Hz
17-14
Rotational Tuning Mode Selection
Range
【0】: VF Mode
【1】: Vector Mode
*1. Values of motor rated voltage are for 200V class, double the values for 400V class.
*2. The setting range of motor rated frequency is 0.0 to 599.0 Hz.