10-10
LED display Description Cause Possible solutions
EF4
(flash)
External fault
(S4)
External fault (Terminal S4)
Active when 03-03= 25 or 68,
and Inverter external fault
selection 08-24=2.
Multifunction digital input
external fault active and
parameter 08-24 = 2 for
operation to continue.
Multi-function input
function set incorrectly.
Check wiring
Multi-function input
function set incorrectly.
Check wiring
EF5
(flash)
External fault
(S5)
External fault (Terminal S5)
Active when 03-04= 25 or 68,
and Inverter external fault
selection 08-24=2.
EF6
(flash)
External fault
(S6)
External fault (Terminal S6)
Active when 03-05= 25 or 68,
and Inverter external fault
selection 08-24=2.
EF9
(flash)
error of
forward/reversal
rotation
Forward run and reverse run
are active within 0.5 sec of
each other. Stop method set
by parameter 07-09.
Forward run and reverse run
active (see 2-wire control).
Check run command
wiring
SE01
Rang setting
error
Parameter setting falls
outside the allowed range.
Some parameter ranges are
determined by other inverter
parameters which could
cause an out of range
warning when the
dependency parameter is
adjusted. For example:
02-00>02-01, 00-12<00-13
or when 00-07 = 1, 00-05 is
the same with 00-06 or
20-16 <= 20-15.
Check parameter setting.
SE02
Digital input
terminal error
Multi-function input setting
error.
Multi-function digital input
terminals (03-00 to 03-07)
are set to the same function
(not including ext. fault and
not used.) or UP/DOWN
commands are not set at
the same time( they must
be used together).
UP/DOWN commands (08
and 09) and ACC/DEC
commands (11) are set at
the same time.
Speed search 1(19
maximum frequency) and
Speed search 2 (34from
the set frequencyare set at
the same time.
2-wire sequence and 3-wire
sequence set at the same
time in 03-00~03-07
Check multi-function input
setting.