10-11
LED display Description Cause Possible solutions
SE03
V/f curve error
V/f curve setting error.
V/F curve setting error.
01-02 > 01-12 > 01-06
(Fmax) (Fbase) (Fmid1)
>01-08;
(Fmin)
Check V/F parameters
SE05
PID selection
error
PID selection error.
10-00 and 10-01are set to 1
(AI1) or 2 (AI2)
simultaneously.
When 23-05=0 and 10-33>=
1000 or 10-341.
Check the setting value of
parameters 10-00 and
10-01.
Check the setting value of
10-33, 10-34 and 23-05.
HPErr
Model selection
error
Inverter capacity setting error:
Inverter capacity setting 13-00
does not match the rated
voltage.
Inverter capacity setting
does not match voltage
class (13-00).
Check inverter capacity
setting 13-00.
SE09
PI setting error
Inverter PI setting error
Inverter pulse input
selection (03-30) selection
conflicts with PID source
(10-00 and 10-01).
Check pulse input
selection (03-30) and PID
source (10-00 and 10-01).
FB
(flash)
PID feedback
breaking
PID feedback signal falls
below level specified in 10-12
(PID feedback loss detection
level) for the time specified in
10-13 (Feedback loss
detection time). Active when
parameter (10-11 = 1).
Feedback signal wire
broken
Feedback sensor broken.
Check feedback wiring
Replace feedback sensor.
USP
(flash)
Unattended
Start Protection
Unattended Start Protection
(USP) is enabled (enabled at
power-up.)
USP at power-up (activated
by multi-function digital
input) is enabled. The
inverter will not accept a
run command.
While the warning is active
the inverter does not
accept a run command.
(See parameter 03-00 -
03-05 = 50).
Remove run command or
reset inverter via
multi-function digital input
(03-00 to 03-07 = 17) or
use the RESET key on the
keypad to reset inverter.
Activate USP input and
re-apply the power.
LFPB
Low flow error
Low flow error
The feedback signal is not
connected.
Due to HVAC feedback
value is lower than limit of
minimum flow.
Check feedback signal is
correct and with right
connection.
Check if feedback value is
lower than limit of
minimum flow.
HFPB
High flow error
High flow error
Due to HVAC feedback
value is lower than limit of
maximum flow.
Check feedback signal is
correct.
Check if feedback value is
lower than limit of
maximum flow.