LED display Description Cause Possible solutions
L0PB
Low pressure
error
Low pressure error
The feedback signal is not
connected.
Due to feedback value of
pump pressure is lower
than limit of minimum flow.
Check feedback signal is
correct and with
connection.
Check if feedback value
of pressure is lower than
limit of minimum
pressure.
HIPB
High pressure
error
High pressure error
Due to feedback value of
pump pressure is lower
than limit of maximum flow.
Check feedback signal is
correct.
Check if feedback value
of pressure is lower than
limit of maximum
pressure.
LSCFT
Low suction
error
Inadequate suction error
Insufficient water of supply
tank leads to insufficient
suction.
PID difference is higher
than its level or current is
lower than output current
level.
Check if water of supply
tank is enough, and water
supply is regular.
Check PID difference is
higher than its level or
current is lower than
output current level
FIRE
Fire override
mode
Fire override mode
Fire override mode is
active
None
(Fire override mode is not
a kind of warning).
SE10
PUMP/HVAC
Setting error
PUMP/HVAC settings of
inverter error
PUMP selection of inverter
(23-02)> (23-03).
HVAC selection of inverter
(23-46)< (23-47).
Check pump selection of
inverter (23-02) and
(23-03) settings.
Check HVAC selection of
inverter (23-46) and
(23-47) settings.
COPUP
PUMP
communication
breaking error
Breaking error of multiple
pumps communication
Communication breaking
or disconnection of pump
cascade control.
Check if it has setting
issue or is not properly
connected.
Parameter
Setting Error
Parameter setting error
Error of Parameter setting
occurs.
Refer to the instruction
manual or this parameter
is selected to be disabled.
Warning of
Direct Start
When 07-04 is set to 1, the
inverter can not start directly
but displays the warning
signal.
Set the digital input
terminal (S1~S6) to run
and simultaneously set
07-04=1.
Check the digital input
terminal and disconnect
it. Then reconnect the DI
terminal after the setting
delay time (07-05) ends.