11-22
Network status LED (COMM LED)
Used to monitor the operability of the communication module PROFIBUS network.
Indicator
statuses
Description
Does not light
up
DP communication
not established
Green light
lights up
DP communication
established and
normal
11.9.5 Driver parameter setting descriptions
Used to monitor the operability of the communication module PROFIBUS network.
Users must first confirm related parameter settings on the driver in order to ensure that
the communication module can connect normally.
Parameters Parameter name Settings Settings descriptions
00-02 Operation command source 2 Communication control
00-05 Frequency command source 3 Communication control