11-30
Function
DIP switch
position
DIP switch
status
7654321
Description
Network
address
Setting
SW1
b7—b1
0000000 Cannot be
used
0000001 Network
address is 1
0000010 Network
address is 2
0000011 Network
address is 3
............ ............
1111110 Network
address is 126
1111111 Network
address is 127
CANopen
Transmission
rate setting
SW2
b3—b1
000 10K
001 20K
010 50K
011 125K
100 250K
101 500K
110 800K
111 1M
Network address switch setting range: 1~127 (0, 128~255 cannot be used).
Transmission rate switch setting range: 0~7 (8~15 cannot be used).
11.10.4 LED indicator descriptions
The module has RUN (green) and ERR (red) indicators built-in used to quickly diagnose
and monitor the communication statuses between the module itself and the bus.