11-47
11.11.6 Troubleshooting
There are two indicators on top of the EtherCAT communication module. When a malfunction
occurs, the cause of the malfunction can be confirmed based on the indicator statuses, and
troubleshoot the error by following the descriptions below.
Indicator troubleshooting
Module status LED2
Indicator
statuses
Status name Troubleshooting method
Does not
light up
Power not supplied
1. Confirm whether the driver power is normal.
2. Confirm whether the power terminal of the
communication module is connected to the
driver.
Red/green
light lights
up
Driver data
transmission error
1. Confirm whether the communication module
has proper contact.
2. Reconnect the power of the driver and
confirm whether the error has been eliminated.
Network status LED1
Indicator
statuses
Status name Description
Does not
light up
Not connected / INIT
1. Confirm whether the driver power is normal.
2. If connected to EtherCAT, confirm whether it is
in INIT mode.
Red light
lights up
Driver data
transmission error
1. Confirm whether the communication module
has proper contact.
2. Reconnect the power of the driver and confirm
whether the error has been eliminated.
11.11.7 xml file
When using the EtherCAT communication module, if the xml description file (JN5-CMHI-ECAT_V
(latest version).xml) is needed, please download it from the TECO official website or request for it
from your purchasing sales channel.