Applied Instructions
Compare a float range with a float value.
EZCP D10 D20 D0
M3
M4
M5
X0
S1· S2·
M3
D1· D2·
The data of S1 is compared to the data of S2. The result is indicated by 3 bit devices specified
with the head address entered as D.
If a constant K or H used as source data, the value is converted to floating point before the
addition operation.
z
z
EZCP K10 K2800 D5 M0
X0
lease set S1<S2, when S2>S1, see S2 as the same with S1 and compare them.
P
Function & Action
(D20, D21) > (D1, D0) ON
Binary Floating Binary Floating
(D21,D10)
≤ (D1,D0) ≤ (D31,D30) ON
Binary Floating Binary Floating Binary Floating
(D1, D0) > (D31, D30) ON
Binary Floating Binary Floating
The status of the destination device will be kept even if the EZCP instruction is deactivated.
(K10) ∶ [D6,D5] ∶ (K2800)→M0,M1,M2
Binary converts Binary Floating Binary converts
to Floating to Floating
[EZCP]
16 bits instruction:- 32 bits instruction:ECMP
Suitable Models:
XC3、XC5
Word
Device
Bit
Device
D
FD
DM
DX
DY
DS
TD
CD
K/H
S1·
S2·
S3·
S1·
S2· S3·
X
Y
M
S
T
C
Dn.m
D·
119