Applied Instructions
TRD D0
X0
Function & Action
The current time and date of the real time
clock are read and stored in the 7 data
devices specified by the head address D.
z Read PLC’s real time clock according to the following format.
The reading source is the special data register D8013~D8019which save
clock data.
[TRD]
16 bits instructionDIV 32 bits instructionDDIV
Suitable Models
XC3XC5
¾
Word
Device
Bit
Device
X Y M S T C Dn.m
D
FD
DM
DX
DY
DS
TD
CD
K/H
Unit Item Clock data
D8018 Year 0-99
D8017 Month 1-12
D8016 Date 1-31
D8015 Hour 0-23
D8014 Minute 0-59
D8013 Second 0-59
Special data register for real
time clock t
D8019 Week 0 (Sun.)-6 (Sat.)
Unit Item
D0 Year
D1 Month
D2 Date
D3 Hour
D4 Minute
D5 Second
D Week
133