7.1.6 103 COMPONENT LEVEL CONFIGURATION REGISTERS
Note: ppp = The specified zero-based preset or load arm number (000-011).
ccc = The specified zero-based component number (000-007).
Modbus:
The Modbus Preset Index Register sets the ppp index, Read/Write Register=996, Len=1, 16-Bit Integer
The Modbus Component Index Register sets the ccc index, Read/Write Register=997, Len=1, 16-Bit Integer
Prefix
Register
Description
Data Type
Min Value
Max Value
Default Value
Protection
Modbus
Register
Len=2
R / U
103000pppccc
Meter#
unsigned int
1
6
1
General
1800
R / U
103001pppccc
High Flow Rate
unsigned int
0
9999
600
General
1802
R / U
103002pppccc
1st Stage Trip Vol
unsigned int
0
65535
70
General
1804
R / U
103003pppccc
1st Stage Flow Rate
unsigned int
0
9999
225
General
1806
R / U
103004pppccc
2nd Stage Trip Vol
unsigned int
0
65535
20
General
1808
R / U
103005pppccc
2nd Stage Flow Rate
unsigned int
0
9999
150
General
1810
R / U
103006pppccc
Final Trip Vol
unsigned div100
0.00
655.35
1.15
General
1812
R / U
103007pppccc
Final Trip Max Time
unsigned div1000
0.000
65.535
5.000
General
1814
R / U
103008pppccc
Final Trip Vol Lock
disable/enable
Disabled
General
1816
R / U
103009pppccc
Unauth Flow Alrm Vol
unsigned int
0
65535
10
General
1818
R / U
103010pppccc
Tank Group
unsigned int
0
9999999
0
General
1820
R / U
103011pppccc
W&M Recipe Percentage
unsigned div 100
0.00
100.00
0.00
W & M
1822
R / U
103012pppccc
Unused
General
1824
R / U
103013pppccc
BlkValve Open Rate
unsigned int
0
9999
0
General
1826
R / U
103014pppccc
BlkValve Open Delay
unsigned int
0
65535
0
General
1828
R / U
103015pppccc
B.V. Open Alrm Time
unsigned int
2
65535
10
General
1830
R / U
103016pppccc
B.V. Close Alrm Time
unsigned int
2
65535
10
General
1832
R / U
103017pppccc
Pump Start Delay
unsigned int
0
65535
3
General
1834
R / U
103018pppccc
Pump Stop Delay
unsigned int
0
65535
30
General
1836
R / U
103019pppccc
Pump Start Alrm Time
unsigned int
2
65535
2
General
1838
R / U
103020pppccc
Flow Start Delay
unsigned int
0
65535
5
General
1840
R / U
103021pppccc
Unused
General
1842
R / U
103022pppccc
Unauth Reset Time
unsigned int
0
65535
0
General
1844
R / U
103023pppccc
Unused
General
1846
R / U
103024pppccc
Fallback Rate
unsigned int
0
9999
350
General
1848
R / U
103025pppccc
Fallback Time
unsigned int
0
65535
0
General
1850
R / U
103026pppccc
Fallback Retry Time
unsigned int
0
65535
0
General
1852
R / U
103027pppccc
Fallback Retry Vol
unsigned int
0
65535
0
General
1854
R / U
103028pppccc
Fallback Minimum Pressure
unsigned div100
0
999999
0
General
1856
R / U
103029pppccc
Fallback Minimum Rate
unsigned int
0
9999
0
General
1858
R / U
103030pppccc
Fallback Increase Rate
unsigned int
0
9999
0
General
1860

Table of Contents