EasyManua.ls Logo

Toptech MultiLoad II - Authorize a Transaction on Multiload; Reading Totalizers

Toptech MultiLoad II
175 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 8 Communication Trace Example
167
...(some time later)...
Sent:(Q) Received: (041CA18)
Modbus:
Fn=0x03, Read Register 7002 -> (0xC61A)
...(some time later)...
Fn=0x03, Read Register 7002 -> (0xCA1A)
Get driver input and terminating key
Sent:(R960) Received: (0419601111)
Sent:(R961) Received: (041961D)
Modbus:
Fn=0x03, Read Registers 2850 ... 2875
8.2.2 AUTHORIZE A TRANSACTION ON MULTILOAD
Authorize transaction on Multiload
Sent:(T_A) Received: (0T1)
Modbus:
Fn=0x06, Write 0 to Register 7016
Enable available presets
Sent:(MEM0002) Received: (0T1)
Sent:(MEM0012) Received: (0T1)
Sent:(MEM0022) Received: (0T1)
Modbus:
Fn=0x06, Write 2 to Register 7032
Fn=0x06, Write 2 to Register 7033
Fn=0x06, Write 2 to Register 7034
Upload the driver number and any other additional information to be included with stored BOL in Multiload
Sent:(U95000004504) Received: (0T1)
Sent:(U9510001234) Received: (0T1)
Sent:(U952 ) Received: (0T1)
Sent:(U953 ) Received: (0T1)
Sent:(U954 ) Received: (0T1)
Modbus:
Fn=0x16, Write data to Registers 2700 … 2724
Fn=0x16, Write data to Registers 2725 … 2749
Fn=0x16, Write data to Registers 2750 … 2774
Fn=0x16, Write data to Registers 2775 … 2799
Fn=0x16, Write data to Registers 2800 … 2824
8.2.3 READING TOTALIZERS
Sent:(R112000) Received:
(0001120000000010000000010000000000000000000000000000000000010000000000000000000000000000
00000000000000000000000000000000000000000000000000000000000000000000000000000000000000000

Table of Contents