Chapter 7 Register Operations
99
7.1.5 102 METER LEVEL CONFIGURATION REGISTERS
Note: ppp = The specified zero-based preset or load arm number (000-011).
mmm = The specified zero-based meter number (000-005).
Modbus:
The Modbus Preset Index Register sets the ppp index, Read/Write Register=996, Len=1, 16-Bit Integer
The Modbus Meter Index Register sets the mmm index, Read/Write Register=998, Len=1, 16-Bit Integer
Prefix
Register
Description
Data Type
Min
Value
Max
Value
Default
Value
Protection
Modbus
Register
Len=2
R / U
102000pppmmm
Flow Control Module#
unsigned int
0
31
0
General
1600
R / U
102001pppmmm
Side-Stream on Mtr#
unsigned int
0
6
0
General
1602
R / U
102002pppmmm
Side Stream on Any Meter
disable/enable
Disabled
General
1604
R / U
102003pppmmm
Unused
General
1606
R / U
102004pppmmm
Meter Address
unsigned int
0
255
0
W & M
1608
R / U
102005pppmmm
Meter Type
meter type
Volume Pulse
W & M
1610
R / U
102006pppmmm
Max Quad Errors
unsigned int
0
65535
10
W & M
1612
R / U
102007pppmmm
Reset Quad Errors
unsigned int
1000
65535
10000
W & M
1614
R / U
102008pppmmm
Low Flow Alarm Rate
unsigned int
0
65535
10
General
1616
R / U
102009pppmmm
Low Flow Alarm Time
unsigned div1000
0.000
999.999
10.000
General
1618
R / U
102010pppmmm
Excess Flw Alrm Rate
unsigned int
0
9999
800
General
1620
R / U
102011pppmmm
Minimum Flow Rate
unsigned int
0
9999
50
General
1622
R / U
102012pppmmm
Maximum Flow Rate
unsigned int
0
9999
650
General
1624
R / U
102013pppmmm
Low Flow DB Rate
unsigned int
0
9999
40
General
1626
R / U
102014pppmmm
High Flow DB Rate
unsigned int
0
9999
40
General
1628
R / U
102015pppmmm
1st Stage DB Rate
unsigned int
0
9999
40
General
1630
R / U
102016pppmmm
2nd Stage DB Rate
unsigned int
0
9999
40
General
1632
R / U
102017pppmmm
Valve Cntl Alrm Time
unsigned div1000
0.000
65.535
10.000
General
1634
R / U
102018pppmmm
Valve Fault Alrm Vol
unsigned int
0
65535
30
General
1636
R / U
102019pppmmm
Creep Reset Time
unsigned int
0
65535
0
General
1638
R / U
102020pppmmm
Ratio Adj P. Factor
unsigned div100
0.00
655.35
10.00
General
1640
R / U
102021pppmmm
Ratio Adj D. Factor
unsigned div100
0.00
655.35
0.30
General
1642
R / U
102022pppmmm
Meter Creep Alrm Vol
unsigned int
0
65535
15
General
1644
R / U
102023pppmmm
Flow Scan Time
unsigned div1000
0.100
1.000
0.100
General
1646
R / U
102024pppmmm
Valve Dwell Time
unsigned div1000
0.010
65.535
1.000
General
1648
R / U
102025pppmmm
Valve Dwell StepRate
unsigned int
0
9999
0
General
1650
R / U
102026pppmmm
Valve Dwell StepTime
unsigned div1000
0.000
5.000
0.000
General
1652
R / U
102027pppmmm
Adaptive Valve Control
disable/enable
Disabled
General
1654
R / U
102028pppmmm
Analog Valve Control
disable/enable
Disabled
General
1656
R / U
102029pppmmm
4-20mA Increase Step
unsigned div 1000
0
4.000
0.080
General
1658
R / U
102030pppmmm
4-20mA Decrease Step
unsigned div 1000
0
4.000
0.800
General
1660