Chapter 7 – Register Operations
10
6
7.1.7 104 – ADDITIVE LEVEL CONFIGURATION REGISTERS
Note: ppp = The specified zero-based preset or load arm number (000-011).
aaa = The specified zero-based additive number (000-0015).
Modbus:
The Modbus Preset Index Register sets the ppp index, Read/Write Register=996, Len=1, 16-Bit Integer
The Modbus Additive Index Register sets the aaa index, Read/Write Register=999, Len=1, 16-Bit Integer
Prefix
Register
Description
Date Type
Min Value
Max Value
Default Value
Protection
Modbus
Register
Len=2
R / U
104000pppaaa
Additive Enable
disable/enable
Enabled
General
2000
R / U
104001pppaaa
Flow Control Module#
unsigned int
0
31
0
General
2002
R / U
104002pppaaa
FCM Port#
unsigned int
0
3
0
General
2004
R / U
104003pppaaa
W&M Controlled
disable/enable
Disabled
W & M
2006
R / U
104004pppaaa
Upstream Block Valve
disable/enable
Disabled
General
2008
R / U
104005pppaaa
Tank Group
unsigned int
0
9999999
0
General
2010
R / U
104006pppaaa
Additive Type
disable/enable
0
4
0
General
2012
R / U
104007pppaaa
Additive P Factor
unsigned div10000
0.0000
10.0000
0.1000
General
2014
R / U
104008pppaaa
Additive I Time
unsigned div10000
0.0000
0.6000
0.3000
General
2016
R / U
104009pppaaa
Additive D Time
unsigned div10000
0.0000
0.6000
0.0000
General
2018
R / U
104010pppaaa
Additive No Flow mA
unsigned div 1000
0.000
20.000
0.000
Conditional
2020
R / U
104011pppaaa
Unused
General
2022
R / U
104016pppaaa
Additive Mode
Additive Mode
NONE
Conditional
2032
R / U
104017pppaaa
Start Volume
unsigned int
0
65535
0
Conditional
2034
R / U
104018pppaaa
Restart Volume
unsigned int
0
65535
0
Conditional
2036
R / U
104019pppaaa
Solenoid Shut Pulses
unsigned int
0
255
0
General
2038
R / U
104020pppaaa
Shutoff Vol From End
unsigned int
0
65535
0
General
2040
R / U
104021pppaaa
LastInj Vol From End
unsigned int
0
65535
20
General
2042
R / U
104022pppaaa
Line Flush Min Vol
unsigned int
0
65535
0
General
2044
R / U
104023pppaaa
Assigned Component
unsigned int
0
8
0
General
2046
R / U
104024pppaaa
W&M Recipe Percentage
percent div 10000
0.0000%
6.5535%
0.0000%
W & M
2048
R / U
104025pppaaa
Add Check Start VOL
unsigned int
0
65535
0
Conditional
2050
R / U
104026pppaaa
Unused
General
2052
R / U
104027pppaaa
Additive Vol/Inject
unsigned div10000
0.0000
6.5535
0.0200
Conditional
2054
R / U
104028pppaaa
Vol/Inject Cal Factr
unsigned div10000
0.0001
6.5535
1.0000
Conditional
2056
R / U
104029pppaaa
Unused
General
2058
R / U
104030pppaaa
Additive Tol Percentage
Percent
0
100.00
0
Conditional
2060
R / U
104031pppaaa
Additive Mtr K-Factr
unsigned int
0
65535
2600
Conditional
2062
R / U
104032pppaaa
Additive Mtr Factor
unsigned div10000
0.0001
6.5535
1.0000
Conditional
2064
R / U
104033pppaaa
Max Pstn Missed Inj
unsigned int
0
65535
0
Conditional
2066
R / U
104034pppaaa
MaxSolenoid Inj Time
unsigned div1000
0.100
10.000
4.000
Conditional
2068
R / U
104035pppaaa
Under Add Alrm # Inj
unsigned int
0
65535
3
Conditional
2070