Chapter 8 Communication Trace Example
164
CHAPTER 8 COMMUNICATION TRACE EXAMPLE
The following is an example of a typical communication session with MultiLoad starting with host system
startup, driver card in, transaction authorization, batch authorization, end of batch processing, and host system
shutdown.
Upon startup it is recommended that the host system verify as many parameters as practical to avoid
problems during loading due to mis-configuration. If any parameters are different then expected the
discrepancy should be logged and startup should be aborted. Recommended parameters to check are:
Firmware Version
Configured bit is set.
Remote Processing is enabled.
Number of configured presets.
Number of meters, components and additives for all presets.
8.1 STARTUP OF HOST SOFTWARE
8.1.1 UPDATE DATE & TIME
Sent:(U001010515153200) Received: (000)
Modbus:
Fn=0x16, Write (YYMMDDHHMMSS) to Registers 35 … 46
8.1.2 UPDATE PRODUCT DEFINITIONS
Start with a clear database and upload base product and additive definitions into indexes 020-099
Sent:(FCLEARPROD) Received: (000)
Sent:(U5000200001100Regular Unlead RUL
02010000000000000000000000000000000000000000000000000000000000000000000000000000000000000
00000000000000000000000) Received: (000)
Sent:(U5000210001300Premium Unlead PUL
02110000000000000000000000000000000000000000000000000000000000000000000000000000000000000
00000000000000000000000) Received: (000)
Sent:(U5000220000600Chevron Additive CHEVADD
02210000000000000000000000000000000000000000000000000000000000000210000000000000000000000
00000000000000000000000) Received: (000)
Sent:(U5000230000700Shell Additive SHEADD
02310000000000000000000000000000000000000000000000000000000000000220000000000000000000000
00000000000000000000000) Received: (000)
Sent:(U5000240000800Generic Additive GENADD
02410000000000000000000000000000000000000000000000000000000000000230000000000000000000000
00000000000000000000000) Received: (000)
Sent:(U5000250000300Base Kerosene KERO
02510000000000000000000000000000000000000000000000000000000000000000000000000000000000000
00000000000000000000000) Received: (000)
Sent:(U5000260001400Base Low Sulfur Diesel BASLSD
02610000000000000000000000000000000000000000000000000000000000000000000000000000000000000
00000000000000000000000) Received: (000)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toptech MultiLoad II and is the answer not in the manual?

Toptech MultiLoad II Specifications

General IconGeneral
BrandToptech
ModelMultiLoad II
CategoryControl Systems
LanguageEnglish

Related product manuals