Chapter 7 Register Operations
13
6
U073DDD.DDD.DDD.DDD => 0?0
Where:
DDD.DDD.DDD.DDD = IP Gateway
Modbus: Read/Write Register=054, Len=2, 32-Bit Integer (4 8-bit numbers)
7.2.9 074 IP HOST
R074 => 0?0074DDD.DDD.DDD.DDD
U074DDD.DDD.DDD.DDD => 0?0
Where:
DDD.DDD.DDD.DDD = IP Host
Modbus: Read/Write Register=056, Len=2, 32-Bit Integer (4 8-bit numbers)
7.2.10 076 ADMIN PASSWORD
Use the Extended Service Register to change the value
7.2.11 077 USER PASSWORD
Use the Extended Service Register to change the value
7.2.12 085 MODEM INITIALIZATION STRING
R085 => 0?0085SSS...
U085SSS… => 0?0
Where:
SSS = ASCII Modem Initialization String (Default "AT&F0&B1&C1&D0S0=1")
Modbus: Read/Write Register=058, Len=40, Characters (SSS…), Null Terminated
7.2.13 091..093 COMMUNICATION PORT PARAMETERS
R09p => 0?009pSDPTAC
U09pSDPTAC => 0?0
Where:
p = Communication Port (1-3)
S = Communication Speed
‘0’ = 300 BAUD
‘1’ = 1200 BAUD
‘2’ = 2400 BAUD
‘3’ = 4800 BAUD
‘4’ = 9600 BAUD
‘5’ = 19.2K BAUD
‘6’ = 38.4K BAUD
‘7’ = 57.6K BAUD
‘8’ = 115K BAUD
‘9’ = 230K BAUD
D = Data Bits
‘0’ = 7 Data Bits

Table of Contents