Chapter 6 Meter Commands
26
CHAPTER 6 METER COMMANDS:
6.1 AUTHORIZE PRESET (PRODUCT AND PRESET VOLUME):
MAMpppaiiivvvvvvvvvcc
Where:
ppp = The specified zero-based preset or load arm number (000-011).
A = Authorize bit, 0 = Cancel Authorization, 1 = Authorize.
Iii = Product Index (500 register) for the authorized product.
Vvvvvvvvv = Preset volume.
Cc = Compartment number.
Note: Will only accept Authorize Preset command when in REMOTE_AUTH_PRESET state or when preset is
authorized and a batch not already authorized.
Modbus:
Write Only Register=7500+5*ppp, Len=1, 16-Bit Integer (iii)
Write Only Register=7501+5*ppp, Len=2, 32-Bit Integer (vvvvvvvvv)
Write Only Register=7503+5*ppp, Len=1, 16-Bit Integer (cc)
Write Only Register=7504+5*ppp, Len=1, 16-Bit Integer (a)
Note: Last Authorize Preset Register Used=7559
6.2 CLEAR ALARMS:
MCAppp by preset
Where:
ppp = The specified zero-based preset or load arm number (000-011).
Modbus:
Write Only Register=7020+ppp, Len=1, 16-Bit Integer (any value)
MCBA by bay
Modbus:
Write Only Register=7019, Len=1, 16-Bit Integer (any value)
6.3 ENABLE PRESET
MEMpppa
Where:
ppp = The specified zero-based preset or load arm number (000-011).
A = Enable Flag, 0 = Disabled, 1 = Enabled/Not Available, 2 = Available
Modbus:
Write Only Register=7032+ppp, Len=1, 16-Bit Integer (a)
6.4 END TRANSACTION
MET
When an ET command is received, a forced card out will occur.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toptech MultiLoad II and is the answer not in the manual?

Toptech MultiLoad II Specifications

General IconGeneral
BrandToptech
ModelMultiLoad II
CategoryControl Systems
LanguageEnglish

Related product manuals