Chapter 2 MultiLoad Responses
13
Since Modbus addressing has been implemented in various ways over the years, to avoid confusion in
this manual, the Modbus Holding Register addresses listed are the value in the register address field in
the message. If it is necessary to know the formal Modbus Holding Register address, simply add 40001
to the register addresses listed in the manual.
1.6.1 READ HOLDING REGISTERS (FN=3)
Note: Both Modbus registers MUST be read at the same time when reading 32-bit values.
Tx:
MBAP
FN=3
Start
Register
MSB
Start
Register
LSB
Number
Of
Registers
MSB
Number
of
Registers
LSB
Rx:
MBAP
FN=3
(+128 if
error)
Byte
Count
1
st
Register
MSB
1
st
Register
LSB
Next
Register
MSB
Next
Register
MSB
1.6.2 WRITE SINGLE REGISTERS (FN=6)
Note: cannot be used for 32-bit registers.
Tx:
MBAP
FN=6
Start
Register
MSB
Start
Register
LSB
Register
MSB
Register
LSB
Rx:
MBAP
FN=6
(+128 if
error)
Start
Register
MSB
Start
Register
LSB
Register
MSB
Register
LSB
1.6.3 LOOPBACK/MAINTENANCE (FN=8)
Note: only loopback of command supported.
Tx:
MBAP
FN=8
Diagnostic
Code MSB
Diagnostic
Code LSB
Data MSB
Data LSB
Rx:
MBAP
FN=8
Diagnostic
Code MSB
Diagnostic
Code LSB
Data MSB
Data LSB
1.6.4 PRESET MULTIPLE REGISTERS (FN=16)
Note: Both Modbus registers MUST be written at the same time when writing 32-bit values.
Tx:
MBAP
FN=16
Start
Register
MSB
Start
Register
LSB
Number
Of
Registers
MSB
Number
of
Registers
LSB
Byte
Count

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toptech MultiLoad II and is the answer not in the manual?

Toptech MultiLoad II Specifications

General IconGeneral
BrandToptech
ModelMultiLoad II
CategoryControl Systems
LanguageEnglish

Related product manuals