Chapter 7 Register Operations
13
9
Modbus:
Not available
7.2.19 129 FCM LOW LEVEL METER STATUS
R129fff => 0?0129fff,pppppppp,kkkk,mmmm,wwww,hhhhhhhh
Where:
fff = FCM number (000-031).
pppppppp = current number of meter pulses received (in hex) in the current active batch.
kkkk = configured Meter K-Factor (in hex).
mmmm = current Meter Factor (in hex, 4 implied decimal places) based on the current flow rate.
wwww = current Weighted Meter Factor (in hex with 4 implied decimal places) in the current
active batch.
hhhhhhhh = current gross delivered volume in hundredths (in hex with 2 implied decimal places)
in the current active batch.
Modbus:
Not available
7.2.20 133 FCM IO ACCESS
R133fffppp => 0?0133fffpppc…
Where:
fff = FCM number (000-031).
ppp = FCM port number (0-35)
c = FCM com, ‘0’ FCM COM ok, ‘1’ FCM COM error.
… = Type Specific Replies
if FCM port number is 0..7, d
Where:
d = State of Digital Port (‘0’ Off, ‘1’ – On)
if FCM port number is 8, fffff
Where:
ffff = Raw frequency/digital value from Opto 22 Analog Module
if FCM port number is 9, sfffff
Where:
sttttt = Temp in Hundreds from Opto 22 RTD Analog Module
(no offset added)
if FCM port number is 10, sttttt
Where:
sttttt = Temp in Hundreds from Toptech RTD Module, FCM II
or I/O Board (no offset added)
Note: All Temps in C or F depending on Register R100003 ("Temps in F").
if FCM port number is 20..35, d (this is used to access I/O board ports and FCM II
expander ports > 7)
Where:
d = State of Digital Port (s-20) (‘0’ – Off, ‘1’ – On)