⎯ 54 ⎯
6 F 2 S 0 7 1 5
When “IRIG” is set, enter the difference between GMT (Greenwich Mean Time) and local time
to convert GMT to local time.
Depending on the relay types, other items are displayed as follows:
Binary input
The logic level of binary input signals can be set to be inverted before entering the scheme logic.
Inversion is used when the open or close condition of the binary input contact does not meet the
contact requirement.
Click the [Binary input] button on the [Setting menu] screen, then the [Binary input] screen will
appear and the binary switch settings can be viewed or changed.
The switches are set to “Norm” (normal) when the input contact condition meets the contact
requirements and set to “Inv” (inverted) when it is not.
Binary output
All the binary outputs are user-configurable except the tripping command, transmitting signal for
command protection and relay failure signal. It is possible to assign one signal or up to six
ANDing or ORing signals to one output relay.