6 F 2 S 0 7 1 5
Status
Click the [Status] button on the [Setting menu] screen, then the [Status] screen will appear and
settings can be viewed or changed on the screen.
Display value:
Enter “Primary” or “Secondary” to display the metering data as primary or secondary values on
the relay LCD.
Power (P/Q):
Enter “Send” or “Receive”, then the active power (P) and reactive power (Q) are signed plus for
power sending or power receiving.
Current:
Enter “Lag” or “Lead”, then the reactive power is signed plus when the current lags or leads the
voltage.
Time sync:
Enter “IRIG” or “RSM”, then the relay clock is synchronized with the IRIG-B time standard
signal or RSM clock. Enter “Off”, then the relay runs locally.
GMT [hour]: