E6582175
K-11
11
Operation mode parameters
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference

0300 PWM carrier
frequency
kHz 0.1/0.1 2.0 -16.0 12.0 6.18

0301 Auto-restart
control selection
- - 0: Disabled
1: At auto-restart after momentary
stop
2: At ST terminal off and on
3: 1+2
4: At start-up
0 5.9

0302 Regenerative
power ride-
through control
(Deceleration
stop)
- - 0: Disabled
1: Regenerative power ride-through
control
2: Deceleration stop during power
failure
3: Synchronized acceleration /
deceleration (signal)
4: Synchronized acceleration /
deceleration (signal + power failure)
0 6.19.2

0303 Retry selection
(number of times)
Times 1/1 0: Disabled
1-10
0 6.19.3

0304 Dynamic braking
selection
- - 0: Disabled
1: Enabled, Resistor overload
protection enabled
2: Enabled
3: Enabled, Resistor overload
protection enabled
(At ST terminal on)
4: Enabled (At ST terminal on)
0 6.19.4

0305 Overvoltage limit
operation
(Deceleration stop
mode selection)
- - 0: Enabled
1: Disabled
2: Enabled (Quick deceleration
control)
3: Enabled (Dynamic quick
deceleration control)
2 6.19.5

0306 Factory specific
coefficient 3L
- - - - * 3

0307 Supply voltage
correction
(output voltage
limitation)
- - 0: Supply voltage uncorrected,
output voltage limited
*1 6.19.6
1: Supply voltage corrected,
output voltage limited
2: Supply voltage uncorrected,
output voltage unlimited
3: Supply voltage corrected,
output voltage unlimited

0308 Dynamic braking
resistance
Ω 0.1/0.1 1.0-1000 *2 6.19.4

0309 Dynamic braking
resistor capacity
kW 0.01/0.01 0.01-30.00 *2

0310 Factory specific
coefficient 3A
- - - -
* 3

0311 Reverse-run
prohibition
- - 0: Forward/reverse run permitted
1: Reverse run prohibited
2: Forward run prohibited
0 6.19.7

0312 Random mode - - 0: Disabled
1: Random mode 1
2: Random mode 2
3: Random mode 3
0 6.18

0314 Factory specific
coefficient 3B
- - - -
* 3
*1: Default setting values vary depending on the setup menu setting. Refer to section 11.5.
*2: Default setting values vary depending on the capacity. Refer to section 11.4.
*3: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of these parameters.

Table of Contents

Other manuals for Toshiba Tosvert VF-S15

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba Tosvert VF-S15 and is the answer not in the manual?

Toshiba Tosvert VF-S15 Specifications

General IconGeneral
CategoryInverter
Control MethodV/f control, Sensorless vector control
Cooling MethodForced air cooling
ModelTosvert VF-S15
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
Communication OptionsModbus RTU
Overload Capacity150% for 1 minute
Braking UnitBuilt-in braking transistor
Output Voltage3-Phase, same as input voltage
Operating Temperature-10 to +50°C (14 to 122°F)
Storage Temperature-20 to 65°C (-4 to 149°F)
Humidity5 to 95% RH (non-condensing)
AltitudeUp to 1000m above sea level
Input Voltage3-Phase 200 to 240 VAC, 3-Phase 380 to 480 VAC