E6582175
D-10
4
4.3.2 Return to default settings
typ : Default setting
Function
It is possible to return groups of parameters to their defaults, clear run times, and record/recall set
parameters.
[Parameter setting]
Title Function Adjustment range Default setting
typ
Default setting
0: -
1: 50Hz default setting
2: 60Hz default setting
3: Default setting 1 (Initialization)
4: Trip record clear
5: Cumulative operation time clear
6: Initialization of type information
7: Save user setting parameters
8: Load user setting parameters
9: Cumulative fan operation time
record clears
10, 11: -
12: Number of starting clear
13: Default setting 2 (complete
initialization)
0
This function will be displayed as 0 during reading on the right. This previous setting is displayed on the left.
Example: 3 0
typ cannot be set during the inverter operating. Always stop the inverter first and then program.
Programmed value
50 Hz default setting (typ=1)
Setting typ to 1 sets the following parameters for base frequency 50 Hz use.
(The setting values of other parameters are not changed.)
• Maximum frequency (fh) : 50Hz • Upper limit frequency (ul) : 50Hz
• Base frequency 1 (vl)
: 50Hz • Base frequency 2 (f170) : 50Hz
• VIA input point 2 frequency (f204) : 50Hz • VIB input point 2 frequency (f213) : 50Hz
• VIC input point 2 frequency (f219) : 50Hz Automatic light-load high-speed operation
• Upper limit of set value (f367) : 50Hz frequency (f330) : 50Hz
• Motor rated speed (f417) : 1410 min
-1
• Communication command point 2 frequency
(f814) : 50Hz