E6582175
D-11
4
60 Hz default setting (typ=2)
Setting typ to 2 sets the following parameters for base frequency 60 Hz use.
(The setting values of other parameters are not changed.)
• Maximum frequency (fh) : 60Hz • Upper limit frequency (ul) : 60Hz
• Base frequency 1 (vl) : 60Hz • Base frequency 2 (f170) : 60Hz
• VIA input point 2 frequency (f204) : 60Hz • VIB input point 2 frequency (f213) : 60Hz
• VIC input point 2 frequency (f219) : 60Hz Automatic light-load high-speed operation
• Upper limit of set value (f367) : 60Hz frequency (f330) : 60Hz
• Motor rated speed (f417) : 1710 min
-1
• Communication command point 2 frequency
(f814) : 60Hz
Default setting 1 (typ = 3)
Setting typ to 3 will return parameters to the default settings (exclusive of some parameters).
When 3 is set, init is displayed for a short time after the settings are configured, and then
disappears. Then the inverter is in standard motor mode. In this case, the trip history data is cleared.
Trip record clear (typ = 4)
Setting typ to 4 initializes the past eight sets of recorded error history data.
The parameter does not change.
Cumulative operation time clear (typ = 5)
Setting typ to 5 resets the cumulative operation time to the initial value (zero).
Initialization of type information (typ = 6)
Setting typ to 6 clears the trips when an etyp format error occurs. But if the  displayed, contact
your Toshiba distributor.
Be aware that the following parameters do not return to the default settings even if typ=3 is set for
maintainability. (To initialize all parameters, set typ=13)
aulOverload characteristic selection f470~f475VIA/VIB/VIC input bias / gain
fmslMeter selection f669Logic output/pulse train output selection
fmMeter adjustment gain f681Analog output signal selection
setChecking the region setting f691Inclination characteristic of analog output
f107Analog input terminal selection f692Analog output bias
f109Analog/logic input selection (VIA/VIB) f750EASY key function selection
f880Free notes
* Refer to “Communication manual” about parameter cxxx.

Table of Contents

Other manuals for Toshiba Tosvert VF-S15

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba Tosvert VF-S15 and is the answer not in the manual?

Toshiba Tosvert VF-S15 Specifications

General IconGeneral
CategoryInverter
Control MethodV/f control, Sensorless vector control
Cooling MethodForced air cooling
ModelTosvert VF-S15
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
Communication OptionsModbus RTU
Overload Capacity150% for 1 minute
Braking UnitBuilt-in braking transistor
Output Voltage3-Phase, same as input voltage
Operating Temperature-10 to +50°C (14 to 122°F)
Storage Temperature-20 to 65°C (-4 to 149°F)
Humidity5 to 95% RH (non-condensing)
AltitudeUp to 1000m above sea level
Input Voltage3-Phase 200 to 240 VAC, 3-Phase 380 to 480 VAC
WeightVaries depending on model (e.g., 0.8 kg to 16 kg)

Related product manuals