Loading...
D301087 0308 - BL20 CANopen 4-139
I/O-Module Objects
4
Object 5420
hex
- Manu Spec Analog Input Range
The object "Manu spec analog input range" defines the parameters
of the analog input channels. Write accesses initiate a parameter
update on the BL20- module bus.
The parameter is stored retentively in the gateway and in the appro-
priate module, and is restored with every node reset.
The Sub-indices 01
hex
– 8E
he
define the parameters for the analog
input channel 1 to 142.
Table 80:
Objects 5420
hex
Feature Description/ Value
Name Manu spec analog input range
Object code ARRAY
PDO-mapping No
Sub-index 00
hex
Data Type Unsigned8
Access ro
Default value, BL20 No
Sub-index 01
hex
to 8E
hex
Data Type Unsigned16
Access rw
Default value, BL20 No

Table of Contents