BL20 - Gateway for CANopen
D301087 0308 - BL20 CANopen3-6
Technical Data
General Technical Data
Relating to a Station
Note
The auxiliary power supply must comply with the stipulations of
SELV (Safety Extra Low Voltage) according to IEC 364-4-41.
Table 1:
General technical
data (station)
Supply voltage/ auxiliary voltage
Nominal value (provision for
other modules)
24 V DC
Permissible range according to EN 61131-2
(18 to 30 V DC)
Residual ripple according to EN 61131-2
Potential isolation Yes, via optocoupler
Ambient conditions
Ambient temperature
–T
Ambient
0 to +55 °C / 32 to 131 °F
–T
Store
-25 to +85 °C / 13 to 185 °F
Relative humidity according to IEC 61 131-2/
EN 50 178
Climatic tests according to IEC 61131-2
Noxious gas SO
2
:
10 ppm (rel. humidity
< 75 %, non-condensing)
–H
2
S:
1.0 ppm (rel. humidity
< 75 %, non-condensing)