EasyManua.ls Logo

turck BL20 - Page 348

turck BL20
461 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
BL20 - Communication in CANopen
D301087 0308 - BL20 CANopen4-276
The following table shows the meaning of the parameter bits:
Byte Design. Status
Comment
Byte 1 Disable
Cfg
Automatic SWIRE configuration
Disabling of the acceptance of the physically present configu-
ration as ACTUAL configuration on manual pushbutton actua-
tion.
0 A Inactive The physically present configuration
of the SWIRE bus is only accepted as
the ACTUAL configuration by
pressing the CFG button. The
comparison with the SET configura-
tion is then carried out
1 Active The physically present configuration
is automatically accepted as the
ACTUAL configuration and then
compared with the SET configuration.
Configu-
ration
PLC configuration check
The configuration check parameter enables a comparison of
the set and actual configuration based on the device ID.
0
A Inactive Configuration check based on device
ID. Only SWIRE slaves with a device
ID completely matching the set
configuration are accepted on the bus
1 Active All slaves are mapped in 4Bit INPUT/
4Bit OUTPUT without checking the
device ID.

Table of Contents