EasyManua.ls Logo

Unipulse F381A - Page 152

Unipulse F381A
164 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
143
9 SUPPLEMENTS
143
SUPPLEMENTS
Chapter
9
*1: Function-specific set values (calibration values, etc.); currently set values remain even if initialization is
executed.
*2: [NOV RAM : N] [SRAM : S]
Item Set value Input range (display range)
Initial
value
Memory
2
Remarks
X-axis Setting
(when the
voltage input
option is
used)
Time/DPM Change 0: Time 1: Displacement Time N
Wave Reference 0: Front 1: Back Front N
Unit
1
See "9-3 Unit setting list" on p.147 mm N
Zero Cal.
1
-5.555 to 5.555 [V] 0.000V N
Equiv. Cal.
1
(voltage value)
-9.999 to 9.999 [V] 5.000V
N
Equiv. Cal.
1
(displacement value)
-99999 to 99999 10.00mm
N
Actual Cal.
1
(displacement value)
-9999 to 32000 10.00mm
N
Measure Length Time/Displacement Change: Time
0 : 0.5s 1 : 1.0s
2 : 2.0s 3 : 5.0s
4 : 10.0 [s]
Time/Displacement Change: Displacement
0 : 2000 1 : 4000
2 : 6000 3 : 8000
4 : 10000
2.0s
60.00mm
N
DPM Positioning -9999 to 32000 0.00mm N
Analog Filter 0 : 10 1 : 30
2 : 100 3 : 300 [Hz]
300Hz
N
Digital Filter 0, 2 to 999 [Times] 0Times N
Option
Setting
Equipment ID
1
0 to 999 0 N
Auto Preserv. 0: Off
1: On (Overwrite)
2: On (Not Overwrite)
Off
N
Preserv. of Set 0 : All Parameter
1 : Comparison Waveform
All
Parameter
Reading of Set 0 : All Parameter (Not Include)
1 : All Parameter (Include)
2 : Comparison Waveform
All
Parameter
(Not Include)
Format
Error Release 0 : Only Release
1 : Annul the Current Data
Only
Release
Communication
Setting
Speed 0 : 1200 1 : 2400
2 : 4800 3 : 9600
4 : 19.2k 5 : 38.4k [bps]
19.2kbps
N
Data Bit 0 : 7 1 : 8 [bit] 8bit N
Stop Bit 0 : 1 1 : 2 [bit] 1bit N
Parity Bit 0 : None 1 : Even
2 : Odd
Even
N
Delimiter 0 : CR 1 : CR+LF CR N
Header 0 : None 1 : STX None N
Flow Control 0 : Off 1 : RTS/CTS Control Off N
Com. Mode 0 : Normal 1 : Hold Point Mode Normal N

Table of Contents

Related product manuals