Configuration and Programming
February 2011 3-16 P/N 06-237041-001
Figure 3-18. FenwalNET 8000-ML Set Menu Functions (Cont’d - Fig. 2 of 14)
3. SET
2. Configuration
3. SLC Devices
1. Device Addr Change
Set SLC Device Address
Present Loop Device Address *_ _ (1-255)
1. Ionization
1. Alarm
1. Fixed Settings
Set Detector Sensitivity
SLC Devices From*__ to __
(1-255)
Set Detector Sensitivity
1: Open Area 2: In Duct 3: DH-2000 *
Set Detector Sensitivity
Pre-Alarm Level *._
(0.5-1.4) %/ft.
Set Detector Sensitivity
Alarm Level *._
(0.5-1.5) %/ft.
2. Day/Night Setting
Set Detector Sensitivity
1: Open Area 2: In Duct 3: DH-2000 *
Set Detector Sensitivity
Pre-Alarm Level *._
(0.5-1.4) %/ft.
Set Detector Sensitivity
Day Alarm Level *._

(0.5-1.5) %/ft.
Set Detector Sensitivity
SLC Devices From*__ to __
(1-255)
Cont’d
*
*=
Level-2 (Installer) Password required .
Set Detector Sensitivity
Night Alarm Level *._

(0.5-1.4) %/ft.
7
SLC Module Selection
Enter SLC Module Number (1-8):_*
Set SLC Device Address
Target Loop Device Address *_ _ (1-255)
SLC Module Selection
Enter SLC Module Number (1-8):_*
SLC Module Selection
Enter SLC Module Number (1-8):_*
2. Supervisory
Set Detector Sensitivity
SLC Devices From*__ to __
(1-255)
Set Detector Sensitivity
1: Open Area 2: In Duct/DH-2000 *
1. Fixed Settings
Set Detector Sensitivity
Alarm Level *._

(0.5-1.5) %/ft.
Set Detector Sensitivity
Day Alarm Level *._

(0.5-1.5 %/ft.
2. Day/Night Settings
Set Detector Sensitivity
Night Alarm Level *._

(0.5-1.4) %/ft.
SLC Module Selection
Enter SLC Module Number (1-8):_*

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the UTC Fire and Security FenwalNET 8000-ML and is the answer not in the manual?

UTC Fire and Security FenwalNET 8000-ML Specifications

General IconGeneral
BrandUTC Fire and Security
ModelFenwalNET 8000-ML
CategoryControl Unit
LanguageEnglish