EasyManua.ls Logo

UTC Fire and Security FenwalNET 8000-ML - CHAPTER 6 TROUBLESHOOTING

UTC Fire and Security FenwalNET 8000-ML
242 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting
P/N 06-237041-001 6-1 February 2011
CHAPTER 6
TROUBLESHOOTING
6-1 INTRODUCTION
This chapter lists all the error messages, their probable causes, and suggested procedures to return
the FenwalNET
8000-ML
TM
System to proper operating condition.
WARNING
Do not attempt any of the corrective actions listed in this chapter until you have:
Physically disconnected the wiring to initiator assemblies (if used) from the release-
circuit terminals, shorted the leads together, and wrapped the leads in insulating tape
Physically disconnected all control heads (if used) from their associated agent storage
container discharge valves
Physically disconnected the wiring to solenoid valves (if used) for pre-action/deluge-
sprinkler systems
Ensured that emergency operations controlled by this system such as facility power
shutoff are bypassed
Notified personnel in the facility and at off-premises monitoring locations that
you are working on the system and that you will inform them when system
servicing has ended.

Table of Contents