Figure 3-19. FenwalNET 8000-ML Set Menu Functions (Cont’d - Fig. 3 of 14)
3. SET
3. SLC Devices
Cont’d
*
2. Configuration
2. Photoelectric
1. Alarm
3. Thermal
*= Level-2 (Installer) Password required .
9
2. Day/Night Setting
Set Detector Sensitivity
SLC Devices From*__ to __
(1-255)
Set Detector Sensitivity
1: Open Area 2: In Duct 3: DH-2000 *
Set Detector Sensitivity
Pre-Alarm Level *._
(0.2-3.4) %/ft.
Set Detector Sensitivity
Day Alarm Level *._
(0.5-3.4) %/ft.
Set Detector Sensitivity
Night Alarm Level *._
(0.5-3.4) %/ft.
SLC Module Selection
Enter SLC Module Number (1-8):_*
Set Detector Sensitivity Spacing
1: 50 ft. 2: 70 ft.*
Set Detector Sensitivity
SLC Devices From*__ to __
(1-255)
Set Detector Sensitivity
Pre-Alarm Level *._
(80-135)
Set Detector Sensitivity
Alarm Level *._
(135-155)
SLC Module Selection
Enter SLC Module Number (1-8):_*
1. Fixed Settings
Set Detector Sensitivity
SLC Devices From*__ to __
(1-255)
Set Detector Sensitivity
1: Open Area 2: In Duct 3: DH-2000 *
Set Detector Sensitivity
Pre-Alarm Level *._
(0.2-3.4) %/ft.
Set Detector Sensitivity
Alarm Level *._
(0.5-3.5) %/ft.
9
SLC Module Selection
Enter SLC Module Number (1-8):_*
2. Supervisory
Set Detector Sensitivity
SLC Devices From*__ to __
(1-255)
Set Detector Sensitivity
1: Open Area 2: In Duct/DH-2000 *
1. Fixed Settings
Set Detector Sensitivity
Alarm Level *._
(0.5-3.5) %/ft.
Set Detector Sensitivity
Day Alarm Level *._
(0.5-3.5 %/ft.
2. Day/Night Settings
Set Detector Sensitivity
Night Alarm Level *._
(0.5-3.4) %/ft.
SLC Module Selection
Enter SLC Module Number (1-8):_*
10