Routings for Power-Limited and Non-Power-Limited
P/N 06-237041-001 E-5 February 2011
Figure E-4. Example Showing Wiring in 2-Tiered Enclosure with Card Cage Assembly (a); Location of knockouts (b)
SLC Card
Relay Card
R-NAC Card
City Tie Card
AC Mains In: Non-Power Limited
SLC Circuits:
Power-Limited
R-NAC 1 & R-NAC 2:
(If Non-Power-Limited
option is used.)
Voltage-Free Relays:
Non-Power-Limited
NOTE:
Route Power-Limited
wiring from RIGHT side
of enclosure.
NOTE:
Route Non-Power-Limited
wiring from LEFT side of
the enclosure (Relays,
R-NAC’s, City Tie-Shunt
Type).
: If Non-Power-
Limited wiring is not being
used, Power-Limited Wiring
can be routed on LEFT side
of the enclosure.
Exception
Keep AC Power wiring from
PMU to PMU dressed snug
against back of enclosure.
Run wires through knockouts as shown to keep
power-limited and non-power-limited outputs separate.
Maintain 1/4-in. separation between power-limited
and non-power-limited wiring. Place non-power-
limited wiring inside a conduit.
Knockout
(b)
(a)
R-NAC 1
R-NAC 2
NAC 1
NAC 2
AUX 1 & AUX 2: Power Limited
NAC 1 & NAC 2: Power Limited
Also
R-NAC 1 & R-NAC 2:
(If Power-Limited option is used.)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the UTC Fire and Security FenwalNET 8000-ML and is the answer not in the manual?

UTC Fire and Security FenwalNET 8000-ML Specifications

General IconGeneral
BrandUTC Fire and Security
ModelFenwalNET 8000-ML
CategoryControl Unit
LanguageEnglish