GENERAL PRECAUTIONS
The following general safety precautions are to be observed at all times:
1. All electrical components associated with equipment shall be installed and grounded in accordance with
NEC and local regulatory requirements.
2. Special precautionary measures are essential to prevent applying power to equipment at any time
maintenance work is in progress.
3. Before working on electrical equipment, use a voltmeter to ensure that system is not energized.
4. When working near electricity, do not use metal rulers, flashlights, metallic pencils, or any other
objects having exposed conductive material.
5. When connecting a meter to terminals for measurement, use a voltage range higher than expected voltage to
be measured.
NOTICE TO USERS, INSTALLERS, AUTHORITIES
HAVING JURISDICTION AND ALL OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for this product to comply with the requirements
in the Standard Control Units and Accessories for Fire Alarm Systems, ANSI/UL 864, certain programming
features or options must be limited to specific values or not used at all as indicated below.
1.) Abort switches may be set up to operate in any of the following ways:
Abort Mode 1
*
(UL) - Count down to 10 seconds and hold. Resume countdown at 10 seconds.
Abort Mode 2 (Reset) - Reset to initial delay setting. Resume countdown for entire delay period.
Abort Mode 3 (IRI) - Same as Mode 1, except disable abort function if countdown timer has started.
Abort Mode 4 (NYC) - Resets to 120 seconds.
Abort Mode 5 - Disables the abort.
*
NOTE:
Only Abort Mode 1 is ANSI/UL 864 compliant.
2.) Event Acknowledgement:
*
NOTE: Global Acknowledge is not ANSI/UL 864 compliant.