Installation
February 2011 2-30 P/N 06-237041-001
2-8.5.1 CROSS ZONE INITIATING DEVICES
Applications which utilize two detectors to initiate the activation of a suppression system, known as
cross or counting zone detection, must comply with the following:
1. Must be acceptable by the local Authority Having Jurisdiction (AHJ).
2. A minimum of two (2) detectors must be used in each protected space.
3. The distance from one detector to another must be 0.7 times the standard linear spacing
determined in accordance with NFPA 72.
4. The Alarm Verification feature cannot be used in cross zoned applications.
The two detector/cross or counting zone configuration is generally used for the actuation of
suppression systems but can also be used as part of an alarm notification system.
2-8.5.2 USE OF ADDRESSABLE OUTPUT MODULES
In order to meet the requirements of UL864 33.1.2.a, the FenwalNET 8000-ML system is limited to
a maximum of 14 addressable output modules that are programmed to activate in response to an
Alarm or Supervisory condition from an SLC-based initiating device. These modules include
SmartOne Model AO Addressable Relay Modules, SmartOne Model ASM Addressable Signal Modules
and SmartOne Remote Releasing Modules.
If RRMs are programmed for grouping release, a maximum of 80 RRMs can be activated within 10
seconds on a single SLC circuit. If RRMs are spread across SLC modules, then 7 groups of 20 RRMs
each can be activated within 10 seconds.