Vertiv | NetSure8200 Series -48 VDC Power System Installation Manual (IM582140000) | Rev. A
136
Block In-Use: Set to the number of 12V battery blocks being used.
Programmable Relay Outputs
The EIB board provides five (5) programmable alarm relays with dry Form-C contacts. Connect up to five (5)
relay outputs to the EIB board. Refer to Figure 85 for terminal locations and Table 9 for pin-out information.
Refer to the NCU instructions (UM1M830BNA) for programming information.
Relay Ratings: Refer to the following.
a) Steady State: 0.5 A @ 60 VDC; 1 A @ 30 VDC.
b) Peak: 3 A @ 30 VDC.
The relays may be preprogrammed for specific functions. Refer to the configuration drawing (C-drawing)
supplied with your system for your system’s specific configuration.
Temperature Probes
Temperature probes can be connected to the EIB board. Refer to Temperature Probeson page 129.