Vertiv | SmartCabinet | User Manual 136
General Maintenance
Table 5-1
SmartCabinet AC
Date: Prepared by:
Model: Serial Number:
Type Maintenance Components Item Result
Monthly Filter Checkforrestrictairow
Checkthelter
Cleanthelter
Indoor unit fan Bearings in good condition
Drain system Check and clean out unit drain pipes
Semi-
annually
Compressor Signs of oil leaks
Vibration isolation
Refrigerant system Suction pressure
Discharge pressure
Superheat
Evaporator in tight and clean condition
Charging capacity of refrigerant
Evidenttemperaturedierencebetweenbefore
andafterthelterdrier
Air-cooled condenser Condenser coil is clean
Motore mounted tightly
Bearing in good condition
Refrigerant pipe properly supported
Electric board Check electrical connections
Check the surface for signs of corrosion
Notes:
Signature:
5.2.2. UPS & Power distribution servicing
The general maintenance for the UPS & Power Distribution system includes Fan Maintenance and Checking
the UPS status.
Fan Maintenance
The UPS fans are intended to run for 20000-40000 hours continuously. The higher the environmental
temperature is, the shorter the fan life tends to be. Verify the fan status periodically on a half-yearly basis
bycheckingiftheairowfromtheventilationholesontherearpaneloftheUPSisappropriateandis
functioning normally.