EasyManua.ls Logo

Vertiv SmartCabinet - 2.3.10. Cable Management & Installation of Accessories

Vertiv SmartCabinet
160 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Vertiv | SmartCabinet | User Manual 49
System Installation
Figure 2-39 shows the illustration of the earth cable connection:
Figure 2-39 Connecting the earth cable
This product is only applicable to the TN system. To ensure safety, the cabinet and AC components
should be grounded properly.
Use a yellow green earth cable of no less than 6 mm² and connect it to the earth copper bar of the com-
puter room accurately.
While xing the M6 screw on the earth hole of the cabinet, Vertiv recommends the use of a wrench.
If an earth block doesn’t exist in the building where the SmartCabinet is placed, use a yellow-green cable
of no less than 6 mm² to connect the earth terminal of the cabinet with that of the PMU total input; this
ensures reliable earthing of the cabinet.
2.3.9. Conguration of the Communication Address and Port
Set the addresses of the 4DIF sensor through the DIP switch, as shown in Figure 2-40 and in Table 2-14:

Table of Contents

Related product manuals