EasyManua.ls Logo

WinGD X92DF - LP SCR Control System Layout

WinGD X92DF
608 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.14.3 LP SCR control system
The main tasks of the WinGD control system for the LP SCR system are as follows:
Calculate the setpoint position for the turbine bypass valve (V4) to control the exhaust
gas temperature.
Control the operation of the auxiliary blowers.
Calculate the setpoint for the urea dosing unit.
Related to the input signals the LP SCR control system gives the related signals to the LP SCR
system, refer to Figure 4-16.
Fig 4-16 LP SCR control system layout
001 002 003
Legend
001 Input signals 003 Output signals
002 LP SCR control system
The main input signals are as follows:
Engine parameters
Prepare Tier III command from RCS
Tier III command from RCS
Position of turbine bypass valve (V4)
Different temperatures and pressures
The main output signals are as follows:
Different temperatures and pressures
Signals to enable or disable the LP SCR system
The principal control configuration of the LP SCR system is shown in Figure 4-17.
X92DF
AA00-9270-00AAA-043B-A
Operation Manual LP Selective catalytic reduction system
Winterthur Gas & Diesel Ltd.
- 110 - Issue 002 2020-08

Table of Contents

Related product manuals