EasyManua.ls Logo

WinGD X92DF - Pressure of the Air Spring Air Supply Is too Low; Oil Leakage Flow in the Collector for Leakage Oil from the Air Spring Is too High; Control Air Supply Pressure Is too Low (Usual Supply); Control Air Supply Pressure Is too Low (Stand-By Supply)

WinGD X92DF
608 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Tab 10-52 Pressure of the air spring air supply is too low
Indication Possible cause Procedure
PT4341A There is an incorrect setting of the
control air supply
Set the control air supply to the correct val-
ue.
There is an incorrect setting of the
safety valve
Set the safety valve to the correct value.
The control air supply is defective
Repair or replace the defective item of the
control air supply.
Tab 10-53 Oil leakage flow in the collector for leakage oil from the air spring is too high
Indication Possible cause Procedure
LS4351-52A The collector for leakage oil from
the air spring is clogged
Clean the collector for leakage oil from the
air spring.
The float control is defective
Repair the float control.
Tab 10-54 Control air supply pressure is too low (usual supply)
Indication Possible cause Procedure
PT4401A The control air supply system is
defective
Find the cause and repair the fault.
There is an incorrect setting of the
control air supply
Set the control air supply to the correct val-
ue.
Tab 10-55 Control air supply pressure is too low (stand-by supply)
Indication Possible cause Procedure
PT4411A The starting air supply system is
defective
Find the cause and repair the fault.
There is an incorrect setting of the
control air supply
Set the control air supply to the correct val-
ue.
Tab 10-56 Control air supply pressure is too low (safety supply)
Indication Possible cause Procedure
PT4421A This is a result of the malfunction
in Table 10-54 - Control air supply
pressure is too low (usual supply)
and in Table 10-55 - Control air
supply pressure is too low (stand-
by supply)
As a temporary procedure, stop the en-
gine.
Do the repair shown there.
The drain valve of the air tank is
open
Close the drain valve of the air tank.
X92DF
AA00-0000-00AAA-410C-A
Operation Manual Malfunctions of systems and components
Winterthur Gas & Diesel Ltd.
- 528 - Issue 002 2020-08

Table of Contents

Related product manuals