Commissioning
48 | WOLF GmbH 3066501_201910
6 Commissioning
DANGER
Escapeofuegases!
Risk of asphyxiation or severe to life-threatening poisoning.
Check that all ue gas accessories have been correctly installed and that none are leaking.
Fill the trap with water.
CAUTION
Oil leak!
Contamination of potable water
Check the system for oil leaks.
NOTE
Oil pump runs dry!
Damage to oil pump.
Check the oil level in the tank and the system.
NOTE
Escaping water!
Water damage.
Check the heat generator and system for leaks.
NOTE
Unqualiedpersonnel!
System damage.
The heat generator may only be commissioned and used for the rst time by a contractor.
The operator must be instructed by a contractor.
6.1 Preparation for commissioning
Check that all ue gas accessories have been correctly installed and that none are leaking.
Unscrew the trap, remove and ll with water.
Water will run out of the drain hole on the side.
Check the system for oil leaks.
Check the oil level in the tank and the system.
Check the heat generator and system for water tightness.
6.2 Putting the heat generator into service
Open the shut-off valves for heating ow and return.
Open oil shut-off valves (tank, oil line, lter).
Switch on the heating emergency stop switch.