Appendix
3066501_201910 WOLF GmbH | 87
12.3.7 Systemconguration60
Cascade for multi-boiler systems
i
Automatic setting if cascade module is connected.
Fig. 12.12 Systemconguration60-Cascadeformulti-boilersystems
q Cascade module
w Feed/heating circuit pump
e Header temperature sensor
Burner starts following a demand from the cascade module via eBus
(0 - 100% burner output; min. to max. within the programmed limit).
Feed/heating circuit pump enabled as a feed pump.
Header temperature control via cascade module
Input E2: not assigned
Automatic output reduction when approaching BTmax (HG22) is enabled. Shutdown when BTmax is
reached
Use a low loss header or plate heat exchanger for hydraulic separation.