Parameter settings
3066501_201910 WOLF GmbH | 57
7 Parameter settings
BM-2 programming unit installation and operating instructions for contractors
AM display module installation and operating instructions for contractors
7.1 Parameter list
i
Changes may only be made by a contractor or WOLF customer service.
NOTE
Improper use!
System faults.
Arrange for a contractor to set and change parameters.
Parameters can only be displayed or changed using the BM-2 programming unit or the AM display
module.
Param-
eter
Description Unit Min. Max. Factory
setting
Individual
setting
HG01 Burner hysteresis °C 7 30 15
HG07 HTG pump run-on (heating mode) min 0 30 1
HG08 Maximum boiler water temperature HTG
T-Flowmax (applicable to heating mode)
°C 40 95 75
HG09 Burner cycle block (applies to heating mode) min 1 30 10
HG10 Bus address - 1 5 1
HG13 Function input E1
(E1 for various functions)
- Various Various None
HG14 Function output A1 (230 VAC)
(A1 for various functions)
- Various Various None
HG15 Cylinder hysteresis °C 1 30 5
HG16 Minimum heating circuit pump rate % 15 100 45
HG17 Maximum heating circuit pump rate % 15 100 100
HG19 CPP run-on time min 1 10 4
HG20 Max. cylinder heating time min 30/OFF 300 120
HG21 Minimum boiler temperature BTmin °C 20 90 20
HG22 Maximum boiler temperature BTmax °C 50 90 80
HG23 Maximum DHW temperature °C 60 80 65
HG25 Excess boiler water temperature during
cylinder heating
°C 0 40 10
HG28 Enable burner stages - Various Various HTG 2 stage
DHW 2
HG33 Burner hysteresis runtime min 1 30 10
HG34 eBus feed - Off On Auto
HG39 Soft start time min 0 10 10
HG40 System conguration - Various Various 1
HG42 Header hysteresis °C 0 20 5
HG43 No function - - - -
HG44 No function - - - -
HG45 No function - - - -
HG46 Excess boiler water temperature, header °C 0 20 6
HG47 CO
2
setting - Variable Variable Variable
HG49 CO
2
setting - Variable Variable Variable
HG56 Input E3:
Only if I/O module is connected.
- Various Various None
HG57 Input E4:
Only if I/O module is connected.
- Various Various None
HG58 Output A3:
Only if I/O module is connected.
- Various Various None