Commissioning
50 | WOLF GmbH 3066501_201910
6.5 Conguringthesystem
BM-2 programming unit installation and operating instructions for contractors
AM display module installation and operating instructions for contractors
The commissioning assistant provides assistance with the following settings:
Standard settings (language, date, time)
User interface simplied / extended
Heating appliance conguration
Conguration of the modules embedded in the eBus
System conguration (7.2.21 HG40: System conguration)
Service message
Pasteurisation function (start time)
Maximum DHW temperature
Set ue gas values (7.2.24 HG47/49: CO
2
setting)
Heating circuit pump venting (6.6.3 Venting the oil pump)
Oil pump venting (6.6.3 Venting the oil pump)
Screed drying
The commissioning assistant is closed automatically after the nal conguration.
To open the commissioning assistant again, perform a reset of the control module.
i
A parameter reset is only possible for control modules connected to the heat generator.
6.6 VentingpumpsandTSstraticationcylinder
6.6.1 Venting feed/heating circuit pump
Installation instructions for feed/heating circuit pump
Check the system pressure.
System pressure over 1.5 bar:
heating circuit is completely vented.
System pressure below 1.5 bar:
Top up with water.
Vent the feed/heating circuit pump again.
6.6.2 VentheatingcircuitoftheTSstraticationcylinder
Activate the DHW demand.
Set the ON/OFF switch of the cylinder primary pump to venting.
Vent the system completely at the maximum system temperature.
Set the cylinder primary pump to constant pressure again.
Fig. 6.3 Cylinder primary pump
q ON/OFF switch
w Venting
e Constant diff. pressure
r Variable diff. pressure