Commissioning
50 | WOLF GmbH 3066501_201910
6.5 Conguringthesystem
BM-2 programming unit installation and operating instructions for contractors
AM display module installation and operating instructions for contractors
The commissioning assistant provides assistance with the following settings:
– Standard settings (language, date, time)
– User interface simplied / extended
– Heating appliance conguration
– Conguration of the modules embedded in the eBus
– System conguration (7.2.21 HG40: System conguration)
– Service message
– Pasteurisation function (start time)
– Maximum DHW temperature
– Set ue gas values (7.2.24 HG47/49: CO
2
setting)
– Heating circuit pump venting (6.6.3 Venting the oil pump)
– Oil pump venting (6.6.3 Venting the oil pump)
– Screed drying
✔ The commissioning assistant is closed automatically after the nal conguration.
► To open the commissioning assistant again, perform a reset of the control module.
A parameter reset is only possible for control modules connected to the heat generator.
6.6 VentingpumpsandTSstraticationcylinder
6.6.1 Venting feed/heating circuit pump
Installation instructions for feed/heating circuit pump
► Check the system pressure.
System pressure over 1.5 bar:
✔ heating circuit is completely vented.
System pressure below 1.5 bar:
► Top up with water.
► Vent the feed/heating circuit pump again.
6.6.2 VentheatingcircuitoftheTSstraticationcylinder
► Activate the DHW demand.
► Set the ON/OFF switch of the cylinder primary pump to venting.
► Vent the system completely at the maximum system temperature.
► Set the cylinder primary pump to constant pressure again.
Fig. 6.3 Cylinder primary pump
q ON/OFF switch
w Venting
e Constant diff. pressure
r Variable diff. pressure